ENTRAVA - Wall Reader Installation

ENTRAVA - Wall Reader Installation

Print

IG4000 Action _ Rev 1.1


NC / NO / Polarity

  • Set-up for Power Off Status
    • NC (Normal Close) – maintain switch connection
    • NO (Normal Open) – maintain switch disconnection

*Definitions according selection of connecting ports


  • Set-up for Operation on Power On Status
    • Polarity – Settled signal for initial status and operation status
    • Delay Time – Keep open for a settled time after authentication, turn back to after settled time pass

*Definitions according to set with special setting card


  • Table by Door Action

Tables can't be imported directly. Please insert an image of your table which can be found here.

 

POLARITY

 

1

0

 

LOCK

NO

NC

Generally Power On standby status is closed

UNLOCK

NC

NO

Door Open status during fixed time


  • Table by Connecting Port

Tables can't be imported directly. Please insert an image of your table which can be found here.

 Port

Polarity 1

Polarity 0

Stand by status

Control

 Stand by status

NC

Open

Connect

Connect

NO

Connect

Open

Open

*Connection=On
*Open=Off


  • IG4000 Default Setting
    • Polarity: 0
    • Delay Time: 3000 msec


Scenario 1 (Emergency exit_1)

  • Lock
    • Lock keep being opened in case Control Wires are Opened (Disconnected)
  • Scenario (Emergency Exit)
    • Door power off - Unlock
    • Stand by status - Lock
    • Door Authentication - Unlock for a while
  • Install & connect
    • Connect to NO port of IG4000
    • Polarity : 1



Scenario 1 (Emergency exit_2)

  • Lock
    • Lock keep being opened in case Control Wires are Closed (Connected)
  • Scenario (Emergency Exit)
    • Door power off - Unlock
    • Stand by status - Lock
    • Door Authentication - Unlock for a while
  • Install & connect
    • Connect to NC port of IG4000
    • Polarity : 1



Scenario 2 (Common Facilities)

  • Facilities Type
    • Lock keep being opened in case Control Wires are Opened (Disconnected)
  • Scenario
    • Door power off - Lock
    • Stand by status - Lock
    • Door Authentication - Unlock for a while
  • Install & connect
    • Connect to NC port of IG4000
    • Polarity : 0


Scenario 3 (Storage)

  • Lock
    • Lock keep being opened in case Control Wires are Closed (Connected)
  • Scenario (Storage)
    • Door power off - Lock
    • Stand by status - Lock
    • Door Authentication - Unlock for a while
  • Install & connect
    • Connect to NO port of IG4000
    • Polarity : 0

Scenario 4 (Elevator all floors)


  • Product : Elevator Button Control
    • Button push action in case Button Common Signal Wire is Closed (Connected)
  • Scenario (Elevator Button)
    • Power off - button is activated
    • In stand by status - button isn’t activated
    • Authentication - Button is activated for a while
  • Install & connect
    • Connect to NC port of IG4000
    • Polarity : 1


Door Lines Connection




Elevator Lines Connection


  • Generally elevator has 2 buttons: up and down
  • There are 2 lines for each of the button, totally 4 lines and two of them should to be connected into the common IG4000 should be connected with this common button line

Tables can't be imported directly. Please insert an image of your table which can be found here.

Pin Name

Abbreviation

Explanation

Pin 1

+12V

 DC 12V power connect

Pin 2

GND

 GND

Pin 3

TMN_T

Door open Switch input Tx Data (Option)

Pin 4

TMN_R

Rx Data (Option)

Pin 5

NO

Normally Open Terminal

Pin 6

COM

Relay Common Terminal

Pin 7

NC

Normally Closed Terminal